M12384-1 v7
Table 126. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
352
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Table 127. Event counter with limit supervision L4UFCNT
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
Table 128. Running hour-meter TEILGAPC
Function
Range or value
Accuracy
Time limit for alarm supervision, tAlarm
(0 - 99999.9) hours
±0.1% of set value
Time limit for warning supervision, tWarning
(0 - 99999.9) hours
±0.1% of set value
Time limit for overflow supervision
Fixed to 99999.9 hours
±0.1%
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB
99