Logic
M12380-1 v12
Table 72. Tripping logic common 3-phase output SMPPTRC
Function
Range or value
Accuracy
Trip action
3-ph, 1/3-ph, 1/2/3-ph
-
Minimum trip pulse length
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
3-pole trip delay
(0.020-0.500) s
±0.2% or ±15 ms whichever is greater
Evolving fault delay
(0.000-60.000) s
±0.2% or ±15 ms whichever is greater
GUID-1E1A829D-1F26-433A-8813-1F5A6F225418 v1
Table 73. Number of SMAGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
SMAGAPC
12
-
-
Table 74. Number of STARTCOMB instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
STARTCOMB
32
-
-
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
Table 75. Number of TMAGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
TMAGAPC
6
6
-
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
Table 76. Number of ALMCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
ALMCALH
-
-
5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
Table 77. Number of WRNCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
WRNCALH
-
-
5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
Table 78. Number of INDCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
INDCALH
-
5
-
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
88
ABB