132kV Busbar
200/5
33kV Busbar
500/5
P
Q
31.5 MVA
ANSI09000040-1-en.vsd
33kV 120V
/
3 3
V
AB
IED
ANSI09000040 V1 EN-US
Figure 191:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure
, it is
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel
PhaseAngleRef
data using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
following table
:
1MRK 505 370-UUS A
Section 14
Monitoring
Busbar protection REB670 2.2 ANSI
437
Application manual