9.2.6
Control
9.2.6.1
Apparatus control
Overview
Under Control in General settings, parameters for Apparatus control can be
adjusted. These are the parameters for among others Bay control, Switch controller,
Reservation input, Circuit breakers and Circuit switches. The parameters include
delay times, dependencies, pulse times and characteristics.
Bay control QCBAY
Main menu/Settings/General settings/Control/ApparatusControl/
BayControl(CBAY)/QCBAY:x
Displays up to six instances of the bay control function QCBAY with a setting that
gives the local operator priority over the remote operator or vice versa.
Bay reserve QCRSV
Main menu/Settings/General settings/Control/ApparatusControl/
BayReserve(CRSV)/QCRSV:x
Displays up to four instances of the bay reserve function QCRSV with nine
parameter settings. The first is for setting the supervision time to cancel a
reservation and the other eight are for the reservation of the own bay only at the
selection of an apparatus.
Circuit breaker SXCBR
Main menu/Settings/General settings/Control/ApparatusControl/
CircuitBreaker(XCBR)/SXCBR:x
Displays available instances of the circuit breaker function with parameter settings
SXCBR for various time limits and pulse lengths. For example, different circuit
breakers may require different pulse lengths to react. The setting
tOpenPulse
is
used to set the length of the pulse required to open a breaker.
Circuit switch SXSWI
Main menu/Settings/General settings/Control/ApparatusControl/
CircuitSwitch(XSWI)/SXSWI:x
Displays available instances of the circuit switch function SXSWI with a number
of settable parameters per instance for time and pulse settings, output reset and
switch type.
Local/Remote switch LocalRemote, LocRemControl
Main menu/Settings/General settings/Control/ApparatusControl/
LocalRemote/LOCREM:x
Section 9
1MRK505209-UEN E
Read and change settings
50
Operator's manual