18000058-IEC19000463-1-en.vsdx
Main protection 2, AR active
(
because main protection 1 not ready)
Main protection 1 not ready
Tr ip CB
Start
Close CB
ZExtension
Def. Tr ip
First AR 1P
Tr ip CB 3P
AR in Pr og.
AR Ready
AR Blocked
Tr ip 3- Pol
Tr ip CB
Start
Close CB
ZExtension
Def. Tr ip
First AR 1P
Tr ip CB 3P
AR in Pr og.
AR Ready
AR Blocked
t Dead1 1P
time < t Oper.
Tr ip 3- Pol
t Discrim. 1P
IEC19000463 V1 EN-US
Figure 59: Timing diagram for scheme with main protections 1 and 2 (REB500sys), both
equipped with an autoreclosure function — Main protection 1 not in operation
>> Response for unsuccessful autoreclosure
Settings:
•
1. AR Mode = 1P-1P or 1P3P-1P3P,
•
2..4. AR Mode = off
•
Zextension = on
•
ZE 1. AR = off
5.8.8
Checking the dead times
GUID-AB1C349F-B540-4E71-B77D-D3DA75A571CE v1
When commissioning the autoreclosure function, it is not sufficient to check the combined
operation of protection function, autoreclosure function and circuit-breaker, the resulting
dead times must also be determined.