Signal
Description
FreqDifOK
Signal indicating that the difference of frequency |df|
between the phases used for checking synchronism has
fallen below the value of the setting of
maxFreqDif.
LiveBus
Signal indicating that the busbar is energized. (U >
minVoltage)
DeadBus
Signal indicating that the busbar is de-energized. (U <
‘maxVoltage’)
LiveLine
Signal indicating that the line is energized. (U > minVoltage)
DeadLine
Signal indicating that the line is de-energized. (U <
maxVoltage)
1) See
.
2) Parts of the function effected by the blocking inputs:
Assuming that both busbar input channels have been configured (double busbars), the active blocking input
depends on the statuses of the binary inputs
uBus1Activ and uBus2Activ:
See
.
Assuming that only the first busbar input channel has been configured —
BlckTrigBus1 and BlckTrigLine are
active.
The active blocking inputs are connected internally to an OR gate and the CB close enabling outputs are
blocked, if one of them is set to
TRUE (T).
3) See
Table 82: uBus1Activ, uBus2Activ
uBus1Activ
uBus2Activ
Selected voltage input
(T) TRUE
(F) FALSE
uBusInput1 active
(F) FALSE
(T) TRUE
uBusInput2 active
Other conditions
The previous blocking input remains active.
Table 83: BlkSynchBus1, BlkSynchBus2, BlkSynchLine
uBus1Activ
uBus2Activ
Selected voltage input
(T) TRUE
(F) FALSE
BlckTrigBus1 and BlckTrigLine
(F) FALSE
(T) TRUE
BlckTrigBus2 and BlckTrigLine
Other conditions
The previous blocking input remains active.
Table 84: OpModeInp1, OpModeInp2
OpModeInp1
OpModeInp2
Operating-Mode
(F) FALSE
(F) FALSE
Mode specified in the control program (Operat.-Mode)
(F) FALSE
(T) TRUE
Synchrocheck OR (bus dead AND line live)
(T) TRUE
(F) FALSE
Synchrocheck OR (bus live AND line dead)
(T) TRUE
(T) TRUE
Synchrocheck OR (bus dead AND line live) OR (bus live
AND line dead)
Section 5
1MRK 505 406-UEN B
Bay protection functions
120
Bay protection functions REB500
Technical manual