OEXPVPH (24) can be connected to any power transformer side, independent
from the power flow.
•
The side with a possible load tap changer must not be used.
8.4.2.2
Operate time of the overexcitation protection
The operate time of OEXPVPH (24) is a function of the relative overexcitation.
Basically there are two different delay laws available to choose between:
•
the so called IEEE law, and
•
a tailor-made law.
The so called IEEE law approximates a square law and has been chosen based on
analysis of the various transformers’ overexcitation capability characteristics. They can
match the transformer core capability well.
The square law is according to equation
.
op
2
2
0.18
0.18
t
M
1
PUV Hz
TD
TD
overexcitation
×
×
=
-
=
æ
ö
ç
÷
è
ø
ANSIEQUATION2298 V2 EN
(Equation 140)
where:
M
the relative excitation
Pickup1 is maximum continuously allowed voltage at no load, and rated frequency, in pu and
TD
is time multiplier for inverse time functions, see figure
.
Parameter TD (“time delay multiplier setting”) selects one delay curve from the family of curves.
The relative excitation M is calculated using equation
measured
measured
rated
measured
measured
rated
M
V
V
f
f
VBase
VBase f
f
=
=
×
æ
ö
ç
÷
è
ø
æ
ö
ç
÷
è
ø
ANSIEQUATION2404 V1 EN
(Equation 141)
1MRK505222-UUS C
Section 8
Voltage protection
533
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...