OVEREXCITATION IN %
Time (s)
IEEE OVEREXCITATION CURVES
en01000373_ansi.vsd
(M-Emaxcont)*100)
TD = 60
TD = 20
ANSI01000373 V1 EN
Figure 273:
Delays inversely proportional to the square of the overexcitation
The critical value of excitation M is determined indirectly via OEXPVPH (24) setting
Pickup2
.
Pickup2
can be thought of as a no-load voltage at rated frequency, where the
inverse law should be replaced by a short definite delay,
t_MinTripDelay
. If, for
example,
Pickup2
= 140 %, then M is according to equation
.
(
)
Pickup2 f
M
1.40
Vn/fn
=
=
ANSIEQUATION2286 V1 EN
(Equation 144)
The
Tailor-Made
law allows a user to design an arbitrary delay characteristic. In this
case the interval between M =
Pickup1
, and M = Mmax is automatically divided into
Section 8
1MRK505222-UUS C
Voltage protection
536
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...