Figure 242: Simplified offset mho characteristics for A-to-B fault in zone 2
Operation occurs if 90° ≤ β ≤ 270°.
Impedance defined in the Figure
2
2
Z Fwd
Z Fwd
ImpedanceAng
=
Ð
2
2
Z R
Z Rev ImpedanceAng
ev
=
Ð
GUID-007D6357-B7CF-4C21-B772-2245F06C83A2 V2 EN-US
(Equation 118)
Voltage and current phasors selected for different measuring loops:
Phase Phase:
Sl.No
Measuring Loop
Voltage Phasor
Current Phasor
1
A-B
VAB
IAB
2
B-C
VBC
IBC
3
C-A
VCA
ICA
Enhanced Reach:
1MRK 502 066-UUS B
Section 7
Impedance protection
443