Figure 240: Logic diagram for the selection of the maximum current loop
The phase-to-ground voltage is compensated with zero sequence voltage in order to avoid the
function operating for ground faults in zone 1, that is, complete generator stator winding and LV
winding of the power transformer.
The reach settings for zone 2 can be provided using the
Z2Fwd, Z2Rev and ImpedanceAng
settings. The
Z2Fwd is forward reach setting and Z2Rev is reverse reach setting. The offset mho
characteristic for phase-to-ground loop is shown in Figure
. The offset mho characteristics for
phase-to-phase loop is shown in Figure
ß
2
I A Z FW
×
1
0
2
Vcomp
V AG V
I A Z FW
=
-
-
×
2
0
2
Vcomp
V AG V
I A Z REV
=
-
+
×
2
I A Z REV
-
×
I A jX
×
I A jX
×
ANSI11000299_1_en.vsd
ANSI11000299 V1 EN-US
Figure 241: Simplified offset mho characteristics for A-to-G fault in zone 2
Section 7
1MRK 502 066-UUS B
Impedance protection
442
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...