-3U
0
=U
ref
Operate area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
a
Characteristic after
angle compensation
RCAcomp
en06000651.vsd
RCADir
= 0º
IEC06000651 V2 EN
Figure 95:
Explanation of RCAcomp
Operation mode 3I
0
· 3U
0
· cosφ
1.
Set the polarizing voltage to 1.2 ·
UNRel>
and the phase angle between
voltage and current to the set characteristic angle (
RCADir
), the current
lagging the voltage.
2.
Measure that the operate power is equal to the
SN>
setting for the set
directional element.
Note that for operation, both the injected current and voltage must be greater
than the set values
INRel>
and
UNRel>
respectively.
The function activates the START and STDIRIN outputs.
3.
Measure with angles
j
=
RCADir
+/- 45° that the measuring element operates
when 3I
0
· 3U
0
· cos (
RCADir
-
j
) = 3I0 · 3U0 · cos(+/-45) =
SN>
.
4.
Compare the result with the set value. Take the set characteristic into
consideration, see figure
5.
Measure the operate time of the timer by injecting 1.2 ·
UNRel>
and a current
to get two times the set
SN>
operate value.
Section 15
1MRK 502 029-UEN A
Verifying settings by secondary injection
176
Installation and commissioning manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Generator protection REG670 Installation and commissioning manual...
Page 2: ......
Page 16: ...10...
Page 24: ...18...
Page 26: ...20...
Page 28: ...22...
Page 92: ...86...
Page 96: ...90...
Page 102: ...96...
Page 108: ...102...
Page 112: ...106...
Page 126: ...120...
Page 140: ...134...
Page 150: ...144...
Page 234: ...228...
Page 238: ...232...
Page 250: ...244...
Page 259: ...253...