These settings define the operating direction for Zones Z3, Z4 and Z5 (the directionality of
zones Z1, Z2 and ZRV is fixed). The options are
Non-directional, Forward or Reverse. The result
from respective set value is illustrated in figure
below, where positive impedance
corresponds to the direction out on the protected line.
IEC05000182-2-en.vsdx
R
X
R
X
R
X
Non-directional
Forward
Reverse
IEC05000182 V2 EN-US
Figure 238: Directional operating modes of the distance measuring zones 3 to 5
tPPZx, tPEZx, TimerModeZx, ZoneLinkStart and TimerLinksZx
Refer to chapter Simplified logic schemes in Technical Manual for the application of these
settings.
OperationSC
Choose the setting value
SeriesComp if the protected line or adjacent lines are compensated
with series capacitors. Otherwise maintain the
NoSeriesComp setting value.
CVTtype
If possible, the type of capacitive voltage transformer (CVT) that is used for measurement
should be identified. Note that the alternatives are strongly related to the type of ferro-
resonance suppression circuit that is included in the CVT. There are two main choices:
Passive type
For CVTs that use a non-linear component, like a saturable inductor, to limit overvoltages
(caused by ferro-resonance). This component is practically idle during normal load and fault
conditions, hence the name ‘passive’. CVTs that have a high resistive burden to mitigate ferro-
resonance also fall in to this category.
Any
This option is primarily related to the so-called active type CVT, which uses a set of reactive
components to form a filter circuit that essentially attenuates frequencies other than the
nominal in order to restrain the ferro-resonance. The name ‘active’ refers to the fact that this
circuit is always involved during transient conditions, regardless of voltage level. This option
should also be used for types that do not fall under the other two categories, for example,
CVTs with power electronic damping devices, or if the type cannot be identified at all.
None
(Magnetic)
This option should be selected if the voltage transformer is fully magnetic.
INReleasePE
This setting opens up an opportunity to enable phase-to-earth measurement for phase-to-
phase-earth faults. It determines the level of residual current (3I0) above which phase-to-earth
1MRK 505 343-UEN B
Section 7
Impedance protection
363
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...