The task time defines the execution repetition rate, and is 1, 3 or 8 ms respectively for the
three task time groups.
SMAI2
BLOCK
REVROT
^GRP2_A
^GRP2_B
^GRP2_C
^GRP2_N
G2AI3P
G2AI1
G2AI2
G2AI3
G2AI4
G2N
ANSI14000028-1-en.vsd
ANSI14000028 V1 EN
Figure 282:
SMAI2 function block
is an example of SMAI2:n to SMAI12:m in each of the three task time groups
1, 2 or 3 where:
•
n=2 and m=12 in task group 1
•
n=14 and m=24 in task group 2
•
n=26 and m=36 in task group 3
The task time defines the execution repetition rate, and is 3, 8 or 1 ms respectively for the
three task time groups.
20.15.3
Signals
Table 613:
SMAI1 Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block group 1
DFTSPFC
REAL
20.0
Number of samples per fundamental cycle used for DFT
calculation
REVROT
BOOLEAN
0
Reverse rotation group 1
GRP1_A
STRING
-
First analog input used for phase A or AB quantity
GRP1_B
STRING
-
Second analog input used for phase B or BC quantity
GRP1_C
STRING
-
Third analog input used for phase C or CA quantity
GRP1_N
STRING
-
Fourth analog input used for residual or neutral quantity
Table 614:
SMAI1 Output signals
Name
Type
Description
SPFCOUT
REAL
Number of samples per fundamental cycle from internal
DFT reference function
G1AI3P
GROUP SIGNAL
Group 1 analog input 3-phase group
G1AI1
GROUP SIGNAL
Group 1 analog input 1
G1AI2
GROUP SIGNAL
Group 1 analog input 2
Table continues on next page
Section 20
1MRK 511 365-UUS A
Basic IED functions
738
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Summary of Contents for Relion 670 Series RES670
Page 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 76: ...70 ...
Page 106: ...100 ...
Page 150: ...144 ...
Page 274: ...268 ...
Page 326: ...320 ...
Page 356: ...350 ...
Page 382: ...376 ...
Page 416: ...410 ...
Page 590: ...584 ...
Page 604: ...598 ...
Page 694: ...688 ...
Page 756: ...750 ...
Page 834: ...828 ...
Page 836: ...830 ...
Page 876: ...870 ...
Page 886: ...880 ...
Page 887: ...881 ...