14.10.8
Technical data
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Table 448:
L4UFCNT technical data
Function
Range or value
Accuracy
Counter value
0-65535
-
Max. count up speed
30 pulses/s (50% duty cycle)
-
14.11
Running hour-meter TEILGAPC
14.11.1
Identification
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter
TEILGAPC
-
-
14.11.2
Functionality
GUID-464FB24F-B367-446C-963A-A14841943B87 v2
The Running hour-meter (TEILGAPC) function is a function that accumulates the
elapsed time when a given binary signal has been high, see also figure
.
Time Accumulation
with Retain
BLOCK
ACC_HOUR
RESET
IN
tWarning
tAlarm
OVERFLOW
WARNING
ALARM
q
-1
a>b
a
b
a>b
a
b
a>b
a
b
&
&
&
q
-1
= unit delay
IEC15000321-1-en.vsd
ACC_DAY
99 999.9 h
tAddToTime
ADDTIME
IEC15000321 V1 EN-US
Figure 322:
TEILGAPC logics
The main features of TEILGAPC are:
•
Applicable to very long time accumulation (≤ 99999.9 hours)
•
Supervision of limit transgression conditions and rollover/overflow
•
Possibility to define a warning and alarm with the resolution of 0.1 hours
•
Retain any saved accumulation value at a restart
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
635
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...