11.4.4.4
Settings
PID-4086-SETTINGS v8
Table 213:
QCBAY Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
AllPSTOValid
Priority
No priority
-
-
Priority
Override Priority of originators,
commands from both local, station and
remote are allowed
RemoteIncStation
No
Yes
-
-
No
Both Station and Remote control are
allowed but not Local when local remote
switch is in remote
11.4.4.5
Operation principle
M13446-4 v7
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay for example, switch control
functions and voltage control functions. The functionality of the Bay control
(QCBAY) function is mainly described by the LLN0 node in the IEC 61850-8-1
edition 2 standard, applied to one bay. In IEC 61850 edition 1 the functionality is
not described by the LLN0 node or any other node, therefore the Bay control
function is represented as a vendor specific node in edition 1.
Local panel switch
M13446-7 v7
The local panel switch is a switch that defines the operator place selection. The
switch connected to this function can have three positions (remote/local/off). The
positions are here defined so that remote means that operation is allowed from
station and/or remote level and local means that operation is allowed from the IED
level. The local/remote switch is also on the control/protection IED itself, which
means that the position of the switch and its validity information are connected
internally, not via I/O boards. When the switch is mounted separately from the IED
the signals are connected to the function via I/O boards.
When the local panel switch (or LHMI selection, depending on the set source to
select this) is in Off position, all commands from remote and local level will be
ignored. If the position for the local/remote switch is not valid the PSTO output
will always be set to faulty state (3), which means no possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch,
the function blocks LOCREM and LOCREMCTRL are needed and connected to
QCBAY.
Permitted Source To Operate (PSTO)
M13446-16 v9
The actual state of the operator place is presented by the value of the Permitted
Source To Operate, PSTO signal. The PSTO value is evaluated from the local/
remote switch position according to Table
. In addition, there are two settings
and one command that affect the value of the PSTO signal.
If the setting
AllPSTOValid
is set to
No Priority
and the LR-switch position is in
Local or Remote state, the PSTO output is set to 5 (all), that is, it is permitted to
1MRK 506 382-UEN A
Section 11
Control
Line distance protection REL650 2.2 IEC
387
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...