operate from local, station and remote level without any priority. When the external
panel switch is in Off position, the PSTO output shows the actual state of the
switch that is, 0. In this case, it is not possible to control anything. The LocSta
command value is forced to
FALSE
if
AllPSTOValid
is set to
No priority
.
If the setting
RemoteIncStation
is set to
Yes
and the LR-switch position is in
Remote state, the PSTO output is set to 2 (Station or Remote), that is, it is
permitted to operate from both station and remote level without any priority.
If the LR-switch position is in Remote state, and
AllPSTOValid
is set to
Priority
and
RemoteIncStation
is set to
No
, the switching between station and remote level
control is done through the command LocSta. The command is accessible only
through the IEC 61850 Edition 2 protocol.
Table 214:
PSTO values for different Local panel switch positions
Local panel
switch positions
AllPSTOValid
(setting)
RemoteInc
Station
(setting)
LocSta.CtlVal
(command)
PSTO
value
LED indications
on LHMI
Possible
locations that
shall be able to
operate
0 = Off
-
-
-
0
Remote and
Local Off
Not possible
to operate
1 = Local
Priority
-
-
1
Remote Off,
Local On
Local Panel
1 = Local
No priority
-
-
5
Remote and
Local On
Local, Station
or Remote
level without
any priority
2 = Remote
Priority
No
TRUE
6
Remote On,
Local Off
Station level
2 = Remote
Priority
No
FALSE
7
Remote On,
Local Off
Remote level
2 = Remote
Priority
Yes
-
2
Remote On,
Local Off
Station or
Remote level
2 = Remote
No priority
-
-
5
Remote and
Local On
Local, Station
or Remote
level without
any priority
3 = Faulty
-
-
-
3
Remote and
Local
Flashing
Not possible
to operate
Blockings
M13446-50 v5
The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.
The blocking facilities provided by the bay control function are the following:
Section 11
1MRK 506 382-UEN A
Control
388
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...