Figure 57:
Simplified block diagram for ZMRPSB function
6.2.6.5
Operating and inhibit conditions
M13877-38 v4
Figure
presents a simplified logic diagram for the Power swing detection
function ZMRPSB. The internal signals DET1of3 and DET2of3 relate to the
detailed logic diagrams in figure
Selection of the operating mode is possible by the proper configuration of the
functional input signals REL1PH, BLK1PH, REL2PH, and BLK2PH.
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh
=
Off
, but notice that the
D
Fw and
D
Rv will still be calculated from
RLdOutFw
and
RLdOutRv
. The characteristic will in this case be only
quadrilateral.
There are four different ways to form the internal INHIBIT signal:
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
129
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...