Basic IED functions
GUID-1DA8FC6E-D726-407B-84D3-0796B00D636F v2
IEC 61850/Function
block name
Function description
Basic functions included in all products
INTERRSIG
Self supervision with internal event list
1
SELFSUPEVLST
Self supervision with internal event list
1
SNTP
Time synchronization
1
TIMESYNCHGEN
Time synchronization
1
DTSBEGIN, DTSEND,
TIMEZONE
Time synchronization, daylight saving
1
IRIG-B
Time synchronization
1
SETGRPS
Setting group handling
1
ACTVGRP
Parameter setting groups
1
TESTMODE
Test mode functionality
1
CHNGLCK
Change lock function
1
TERMINALID
IED identifiers
1
PRODINF
Product information
1
PRIMVAL
Primary system values
1
SMAI_20_1-12
Signal matrix for analog inputs
2
3PHSUM
Summation block 3 phase
12
GBASVAL
Global base values for settings
6
ATHSTAT
Authority status
1
ATHCHCK
Authority check
1
FTPACCS
FTP access with password
1
DOSFRNT
Denial of service, frame rate control for front port
1
DOSLAN1
Denial of service, frame rate control for LAN1
1
DOSSCKT
Denial of service, socket flow control
1
4. Differential protection
Restricted earth fault protection REFPDIF
1Ph High impedance differential protection HZPDIF
(87)
M13071-3 v8
The 1Ph High impedance differential protection (HZPDIF,
87) function can be used when the involved CTs have the
same turns ratio and similar magnetizing characteristics.
It utilizes an external summation of the currents in the
interconnected CTs, a series resistor, and a voltage
dependent resistor which are mounted externally
connected to the IED.
Three instances of 1Ph High impedance differential
protection function (HZPDIF, 87) can be used to provide a
three phase differential protection function to be used for
example as busbar protection. One instance of HZPDIF
(87) can also be used as high impedance REF protection.
5. Current protection
Four step phase overcurrent protection OC4PTOC
(51/67)
M12846-3 v9
The four step phase overcurrent protection function
OC4PTOC (51/67) has independent inverse time delay
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
ABB Power Grids
9