M12702-1 v4
Table 40. Event recorder DRPRDRE
Function
Value
Buffer capacity
Maximum number of events in
disturbance report
150
Maximum number of disturbance
reports
100
Resolution
1 ms
Accuracy
Depending on time synchronizing
M13747-1 v5
Table 41. Trip value recorder DRPRDRE
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance
reports
100
M12384-1 v5
Table 42. Disturbance recorder DRPRDRE
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum
number of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
GUID-F633E33E-D602-4C21-8E39-2EBC8DA19863 v3
Table 43. Station battery supervision SPVNZBAT
Function
Range or value
Accuracy
Lower limit for the battery terminal voltage
(60-140) % of Vbat
± 1.0% of set battery voltage
Reset ratio, lower limit
<105 %
-
Upper limit for the battery terminal voltage
(60-140) % of Vbat
± 1.0% of set battery voltage
Reset ratio, upper limit
>95 %
-
Timers
(0.000-60.000) s
± 0.5% ± 110 ms
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
ABB Power Grids
37