swell time 1
or
VVa Int time 1
, depending on the variation type, and
VVa Dur Max
). The
maximum variation duration setting is the same for all variation types.
shows voltage dip operational regions. In
swell/Int set is drawn, whereas in this figure there are three sub-limits for the dip
operation. When
Voltage dip set 3
is undershot, the corresponding
ST_x
and also the
DIPST
outputs are activated. When the TRMS voltage magnitude remains between
Voltage dip set 2
and
Voltage dip set 1
for a period longer than
VVa dip time 2
(shorter time
than
VVa dip time 3
), a momentary dip event is detected. Furthermore, if the signal
magnitude stays between the limits longer than
VVa dip time 3
(shorter time than
VVa Dur
max
), a temporary dip event is detected. If the voltage remains below
Voltage dip set 1
for
a period longer than
VVa dip time 1
but a shorter time than
VVa dip time 2
, an
instantaneous dip event is detected.
For an event detection, the
TRIP
output is always activated for one task cycle. The
corresponding counter and only one of them (INSTDIPCNT, MOMDIPCNT or
TEMPDIPCNT) is increased by one. If the dip limit undershooting duration is shorter than
VVa dip time 1
,
VVa swell time 1
or
VVa Int time 1
, the event is not detected at all, and if
the duration is longer than
VVa Dur Max
, MAXDURDIPCNT is increased by one but no
event detection resulting in the activation of the
TRIP
output and recording data update
takes place. These counters are available through the monitored data view on the LHMI
or through tools via communications. There are no phase-segregated counters but all the
variation detections are registered to a common time/magnitude-classified counter type.
Consequently, a simultaneous multiphase event, that is, the variation-type event detection
time moment is exactly the same for two or more phases, is counted only once also for
single-phase power systems.
GUID-0D3F6D81-F905-4D8D-A579-836EF7BB6773-ANSI V1 EN
Figure 532:
Voltage dip operational regions
, the corresponding limits regarding the swell operation are provided with
the inherent magnitude limit order difference. The swell functionality principle is the
same as for dips, but the different limits for the signal magnitude and times and the
inherent operating zone change (here,
Voltage swell set x
> 1.0 xVn) are applied.
1MAC059074-MB A
Section 10
Power quality measurement functions
615 series ANSI
1045
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......