![ABB Relion 615 series Modbus Point List Manual Download Page 94](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023094.webp)
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
u16
1000
.A.phsA.cVal.mag
Max demand IL1
Phs A amplitude
0.00…50.0
[xIn]
u16
1000
.A.phsB.cVal.mag
Max demand IL2
Phs B amplitude
0.00…50.0
[xIn]
u16
1000
.A.phsC.cVal.mag
Max demand IL3
Phs C amplitude
0.00…50.0
[xIn]
2.4.1.30
LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
Table 153:
LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CMMXU1
Phase current (1)
138
u16
1000
.A.phsA.instCVal.mag
I_INST_A
Phs A amplitude
0.00...40.0
[xIn]
139
u16
1000
.A.phsB.instCVal.mag
I_INST_B
Phs B amplitude
0.00...40.0
[xIn]
140
u16
1000
.A.phsC.instCVal.mag
I_INST_C
Phs C amplitude
0.00...40.0
[xIn]
2.4.1.31
LD0.CSMSQI1 Sequence current measurement (1) – I1, I2, I0
Table 154:
LD0.CSMSQI1 Sequence current measurement (1) – I1, I2, I0
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.CSMSQI1
Sequence of currents
143
u16
1000
.SeqA.c1.instCVal.mag
I1_INST
Positive amplitude
0.00...40.0
[xIn]
144
u16
1000
.SeqA.c2.instCVal.mag
I2_INST
Negative amplitude
0.00...40.0
[xIn]
145
u16
1000
.SeqA.c2.instCVal.mag
I3_INST
Zero amplitude
0.00...40.0
[xIn]
2.4.1.32
LD0.FMMXU1 Frequency measurement (1) – f-1
Table 155:
LD0.FMMXU1 Frequency measurement (1) – f-1
RegA
Type
Scale
IEC 61850 name
SA name
Description
Values
LD0.FMMXU1
146
u16
100
.Hz.mag
F_DB
Frequency
35.00..75.00
[Hz]
Section 2
1MAC252756-MB B
Modbus data mappings
88
REM615 ANSI
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Page 2: ......
Page 14: ...8...
Page 114: ...108...