![ABB Relion 615 series Modbus Point List Manual Download Page 50](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_modbus-point-list-manual_3381023050.webp)
BitA
RegA
IEC 61850 name
SA name
Description
Values
2897
181.01
.mcd
2898
181.02
.Op.general
TRIP
General trip
1=Trip
2899
181.03
.mcd
2.3.1.62
LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low
stage (1) – 51P-1
Table 65:
LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1) – 51P-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0.PHLPTOC1
2880
180.00
.Str.general
PICKUP
General pickup
1=Pickup
2881
180.01
.mcd
2882
180.02
.Str.phsA
Phs A pickup
1=Pickup
2883
180.03
.mcd
2884
180.04
.Str.phsB
Phs B pickup
1=Pickup
2885
180.05
.mcd
2886
180.06
.Str.phsC
Phs C pickup
1=Pickup
2887
180.07
.mcd
2888
180.08
.Op.general
TRIP
General trip
1=Trip
2889
180.09
.mcd
2.3.1.63
LD0.PHPTOV1 Three-phase overvoltage protection (1) – 59-1
Table 66:
LD0. PHPTOV1 Three-phase overvoltage protection (1) – 59-1
BitA
RegA
IEC 61850 name
SA name
Description
Values
LD0. PHPTOV1
4026
251.1
.Str.general
PICKUP
General pickup
1=Pickup
4027
251.11
.mcd
.Str.phsA
phsA pickup
1=Pickup
.mcd
.Str.phsB
phsB pickup
1=Pickup
.mcd
.Str.phsC
phsC pickup
1=Pickup
.mcd
4028
251.12
.Op.general
TRIP
General trip
1=Trip
4029
251.13
.mcd
Section 2
1MAC252756-MB B
Modbus data mappings
44
REM615 ANSI
Point List Manual
Summary of Contents for Relion 615 series
Page 1: ...RELION 615 SERIES Motor Protection and Control REM615 ANSI Modbus Point List Manual...
Page 2: ......
Page 14: ...8...
Page 114: ...108...