ABB Relion 611 Series Quick Start Manual Download Page 2

2

QU I CK STA RT G U I DE 

R EL I O N ®  61 1  SER I E S

Using the local HMI

Accessing main menu and changing parameters
Press   to navigate to the main menu from the measurements 

view.

From the main menu, go to 

Settings

 and press 

Then press   or   to select the setting value you want 

to change. Press   to change it with   or   buttons. 

If there is a “#” mark on the same line as the parameter value, 
you have to first select which setting group parameter you 
want to change. If there is no “#” mark then you can change 
the value directly by pressing   and then with   or   or  

 or 

 buttons.

You can change all parameters in the same way. The most 
common function block names are described at the end of 
this document.

Storing settings
Parameters have to be stored before taken into use. 
Store the settings by going back to the main menu by pressing 
the 

 button. The IED will ask for confirmation to commit 

changes, answer “Yes“. Some changes require the IED to reboot 
before the changes are taken into use. Reboot the IED by going 
to main menu 

Configuration → General → Software reset

 

or by switching the auxiliary power off and back on.

Changing the overcurrent start value
From the main menu, go to 

Settings → Settings → select 

setting group, default 1

 and press   

→ Current Protection → 

PHLPTOC1 → Start value

.

Changing function block naming from IEC 61850 names 
to IEC 60617
From the main menu, go to 

Configuration → HMI → 

FB Naming convention

.

Checking binary input value
From the main menu, go to 

Monitoring → I/O Status → 

Binary input values → select correct BIO card

.

Checking fault records and measurement values of 
the latest faults
From the main menu, go to 

Monitoring → Recorded data → 

Fault record

.

Clearing events, indications and programmable LEDs
From the main menu, go to 

Clear

. Select the item you want to 

clear and press   and select Clear by pressing   (Cancel 

will disappear). Confirm by pressing  .

Checking IED order code, serial number, HW revision and 
software version
From the main menu, go to 

Information → Product Identifiers

.

Display header area
The icon area at the upper right corner of the dislay shows 
the current action or user level. These are described below:
S  =  Parameters are being stored
!   =  Warning and/or indication
V  =  Viewer
O =  Operator
E  =  Engineer
A  =  Administrator

Checking the input and output status of a function block
From the main menu, go to 

Monitoring → I/O status

.

Checking the IP address
The address of the front communication port is fixed: 
192.168.0.254. If the IED is equipped with a communication 
card you can check the IP address of the rear communication 
port from the main menu 

Configuration → Communication → 

Ethernet → Rear port(s)

.

Activating the Web HMI
To activate the Web HMI from the main menu go to 

Configuration → HMI → Web HMI mode

. Activation requires 

rebooting the IED.

Changing the display contrast
Hold   and press   or   to change the display contrast. 

The display contrast setting is automatically stored when A 
(Administrator) is visible in the icon area at the upper right 
corner of the display.