Phase-ground fault
ANSI11000119_1_en.vsd
0line
3I
ANSI11000119 V1 EN
Figure 34:
Single phase-to-ground fault
6.
Set
tVN
to
0.001 s
Setting
tVN
gives the pick-up delay for residual voltage. The default value
0.001 s
is
proposed.
7.
Set
tOffVN
to
0.1 s
Setting
tOffVN
gives the drop-off delay for residual voltage. The default value 0.1 s
is proposed.
Set
tOffVN
to
0.1 s
8.
Set
tIN
to
0.15 s
Setting
tIN
gives the pick-up delay for residual current. The default value
0.15 s
is
proposed.
3.2.2
Calculating settings for sensitive directional residual
overcurrent protection SDEPSDE 67N
In high impedance grounded system the ground fault current, at single phase-to-ground
fault, is small compared to the fault current at phase-to-phase short circuit. Therefore it is
difficult and normally not possible to use distance protection as ground fault protection.
In many networks it is also required to detect and clear phase-to-ground faults with a high
resistance to ground in the fault point. The ground fault current is limited by the
1MRK 506 334-UUS A
Section 3
REL650 setting examples
85
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...