Table 6:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
•
Follow-S sequence: The activation signal is on.
•
LatchedColl-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
•
LatchedAck-F-S sequence: The indication has been acknowledged, but the activation
signal is still on.
•
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
•
LatchedReset-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
Flashing
•
Follow-F sequence: The activation signal is on.
•
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
•
LatchedAck-S-F sequence: The indication has been acknowledged, but the activation
signal is still on.
5.1.4.2
Parameter management
The LHMI is used to access the IED parameters. Three types of parameters can be read and
written.
•
Numerical values
•
String values
•
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum and
maximum values. Character strings can be edited character by character. Enumerated
values have a predefined set of selectable values.
5.1.4.3
Front communication
The RJ-45 port in the LHMI enables front communication.
•
The green uplink LED on the left is lit when the cable is successfully connected to the
port.
1MRK 506 334-UUS A
Section 5
Local human-machine interface
111
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...