72
Preparing for test
Chapter 11
Verifying settings by secondary
injection
3.
Select ‘No’.
4.
Press ‘C’ twice to leave the menu.
The ‘Save TestGroup?’ dialog appears.
5.
Choose ‘Yes’ leave the menu.
2.7
Checking the disturbance report settings
The terminal must be set in testmode (Operation=ON) to activate the disturbance report
settings.
The user can select how the disturbances are indicated on the local HMI during the test.
The user can for example select if the disturbance summary should be stored, scrolled
on the local HMI or if LED information should be stored. Scroll to the disturbance re-
port settings which are located in the local HMI under: