Overview
Chapter 9
Setting and configuring the terminal
1
Overview
The customer specific values for each setting parameter and a configuration file has to
be available, if the terminal is not delivered with a configuration, before the terminal
can be set and configured.
Each function included in the terminal has several setting parameters which has to be
set in order to make the terminal behave as intended. A default value is provided for
each parameter from factory. A setting file can be prepared using the parameter setting
tool (PST), which is available in the CAP 535 package.
Use the CAP 531 configuration tool to verify if the terminal has the expected configu-
ration. A new configuration is performed with the CAP tool. The binary outputs can be
selected from a signal list where the signals are grouped under their function names. It
is also possible to specify a user-defined name for each input and output signal.
All settings can be:
•
Entered manually through the local HMI.
•
Downloaded from a PC, either locally or remotely using SMS/SCS. Front or rear
port communication has to be established before the settings can be downloaded.
The configuration can only be downloaded through the front connector on the local
HMI.
Note!
Be sure to configure the functional input HMI--BLOCKSET to only one of the available
binary inputs before setting the parameter SettingRestrict to Block in the local HMI.