Quick Start Guide For The DNP Orion To ABB REL 356 Relays Using Modbus
12
appear on the LED. Figure 13 illustrates the menu selection for download selection.
+--------------¦ NovaTech Conitel-Modbus Configuration Program ¦---------------+
¦ PRINTER: READY FILE NAME: TEST.CTL ¦
¦ File Setup Memory Map Transfer About 10:36:58 ¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦+--------------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦ Run MMI ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦ DownLoad -> ¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦ UpLoad <-¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦+--------------+¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦¦
¦+----------------------------------------------------------------------------+¦
¦¦Current Video Mode = 80x25 ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦¦ ¦¦
¦+-----------------------------¦ Message Window ¦-----------------------------+¦
+------------------------------------------------------------------------------+
Open Window to Run the Protocol Converter MMI
Figure 13 – Transfer And Debug Configuration Screen
16.
The ORION Unit is now configured for communication to both the Conitel Host and the Modbus IED.
When the Conitel Host polls the ORION unit, the Red TX and RX LED’s shall illuminate on a Host
Transmission and ORION Response. To observe the communication strings sent/received by the
ORION, by selecting the “RUN MMI” menu item as illustrated in Figure 13, shall reveal the following
menu items displayed upon the PC screen.
PRESS ANY KEY TO CONTINUE
POLLING STATUS: CONITEL OFF, ADDR 1, MODBUS OFF.
1)
TOGGLE CONITEL PORT DISPLAY, CURRENTLY OFF.
2)
TOGGLE MODBUS PORT DISPLAY, CURRENTLY OFF.
M)
MODEM SETUP and TEST MENU
S) DISPLAY COMMUNICATION STATISTICS.
Please enter your Selection:
17.
Depress “2” to select the Modbus Port Display , the menu should be redisplayed with the status of
the port.
18.
Depress “S” to display the communication strings sent and received over the ORION IED port. The
status of the communication statistics sends and replies will also be displayed.
19.
Depress 1 to select the Conitel Port Display strings sent and received over the ORION SCADA port.
20.
If the software or hardware configuration or setups of the unit are incorrect, the unit may not report a
response or a transmission. Refer to Table 1 of this document to aid in troubleshooting the ORION
installation.
21.
If the PORT CONFIGURATION and the CONITEL/MODBUS point mapping is correct, the data
strings will reveal the Modbus/CONITEL commands sent/received over the network. The total of
commands, sent/received shall be approximately the same.