Quick Start Guide For The DNP Orion To ABB REL 356 Relays Using Modbus AN-55A-00
11
14.
For this “QUICK START” example, Conitel Input AI shall be configured for a DPU 2000R device
attached to the IED port. If the DPU 2000R Modbus document is reviewed, Phase A, B,and C, load
currents and their respective load angles are located at eight consecutive registers beginning at
40257 through 40264 and they shall be remapped to the Conitel blocks 1b through 5a. The Conitel
SCAN INPUT command shall access these blocks. After selection of all parameters, simultaneously
depress the “CONTROL and ENTER” key on the configuration terminal’s keyboard.
+--------------¦ NovaTech Conitel-Modbus Configuration Program ¦---------------+
¦ PRINTER: READY FILE NAME: TEST.CTL ¦
¦ File Setup Memory Map Transfer About 10:38:33 ¦
¦¦¦¦¦¦¦¦¦¦¦+-----------¦ Standard Modbus-Conitel Input ¦-----------+¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦ ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦ Conitel Data Type: AI ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦ Point Description: Analog Input #1 ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦ Conitel Group: 1 ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦¦¦¦¦¦¦¦¦¦¦¦ Conitel Point Start: 1 ¦¦¦¦¦¦¦¦¦¦¦¦¦
¦+---------¦ Number of Conitel Points: 8 ¦----------+¦
¦¦Current V¦ Conitel Section Start: 1b ¦ ¦¦
¦¦ ¦ Conitel Section End: 5a ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ MODICON PLC Address: 2 ¦ ¦¦
¦¦ ¦ Start Modbus Register: 40257 ¦ ¦¦
¦¦ ¦ Number of Registers: 8 ¦ ¦¦
¦¦ ¦ Zero Value: 0.0000 ¦ ¦¦
¦¦ ¦ Span Value: 400.00 ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ ¦ ¦ ¦¦
¦¦ +-------------------------------------------------------+ ¦¦
¦+-----------------------------¦ Message Window ¦-----------------------------+¦
+------------------------------------------------------------------------------+
<Tab>: Next Field <Esc>: Abort <Ctrl>+<Enter>: Accept
Figure 8 – Analog Input Mapping Screen
15.
The configuration files must now to be downloaded to the ORION unit. Select the TRANSFER
menu and then select the Download Option. The following screen should be displayed. When the
parameters are accepted by the ORION, an indication shall be shown on the screen. Additionally,
the amber CONFIG LED at the front panel of the unit shall not flash. A constant illumination shall