16.6.2
Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.
16.6.3
Function block
IEC10000250-1-en.vsd
GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V1 EN
Figure 291:
GOOSEINTRCV function block
16.6.4
Signals
Table 472:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 473:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
16.6.5
Settings
Table 474:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
16.6.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
1MRK 502 048-UEN A
Section 16
Station communication
605
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...