Table 36. Transient/intermittent earth-fault protection (INTRPTEF) main settings
Parameter
Function
Value (Range)
Step
Directional mode
INTRPTEF
1=Non-directional
2=Forward
3=Reverse
-
Operate delay time
INTRPTEF
0.04...1200.00 s
0.01
Voltage start value
(voltage start value
for transient EF)
INTRPTEF
0.005...0.500 pu
0.001
Operation mode
INTRPTEF
1=Intermittent EF
2=Transient EF
-
Peak counter limit
(Min requirement for
peak counter before
start in IEF mode)
INTRPTEF
2...20
1
Table 37. Negative phase-sequence overcurrent protection (NSPTOC)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
I
Fault
= 2 × set
Start
value
I
Fault
= 10 × set
Start
value
Typical 23 ms (±15 ms)
Typical 16 ms (±15 ms)
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50dB at f = n × f
n
, where n = 2, 3, 4, 5,
…
1)
Operate curve type
= IEC definite time, negative sequence current before fault = 0.0, f
n
= 50Hz
2) Includes the delay of the signal output contact
3) Maximum
Start value
= 2.5 × I
n
,
Start value
multiples in range of 1.5 to 20
Feeder Protection and Control
1MRS756380 A
REF630
Product version: 1.0
Issued: 15.09.2009
34
ABB