Table 31. Non-directional earth-fault protection (EFxPTOC)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
EFLPTOC
±1.5% of the set value or ±0.001 x I
n
EFHPTOC
and
EFIPTOC
±1.5% of set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Start time
1)2)
EFIPTOC:
I
Fault
= 2 x set
Start
value
Typical 12 ms (±5 ms)
EFHPTOC:
I
Fault
= 2 x set
Start
value
Typical 19 ms (±5 ms)
EFLPTOC:
I
Fault
= 2 x set
Start
value
Typical 23 ms (±15 ms)
Reset time
< 45 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,
…
Peak-to-Peak: No suppression
1)
Operate curve type
= IEC definite time,
Measurement mode
= default (depends on stage), current before fault =
0.0 x I
n
, f
n
= 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value
= 2.5 x I
n
,
Start value
multiples in range of 1.5 to 20
Feeder Protection and Control
1MRS756380 A
REF630
Product version: 1.0
Issued: 15.09.2009
30