Feeder Terminal
REF 542plus
1MRS756269
6
Application
Monitoring and self-diagnosis
The REF 542plus offers several features for
monitoring the primary part as well as self-
diagnosis. The following computed quantities
are available for primary part monitoring:
•
maximum and mean currents in the obser-
vation period (0 ... 30 min)
•
sum of interrupted currents
•
operating time
•
number of switching cycles (open-close
circuit breaker)
•
spring charging time supervision (when
applicable)
•
trip coil supervision
The REF 542plus is equipped with self-diag-
nosis routines that constantly check the hard-
ware and software modules status. Every
REF 542plus binary input and output module
is equipped with a watchdog contact that trig-
gers in case of fault or power loss. This con-
tact can be used to detect unit failure and to
initiate the appropriate actions. Analog input
channels can be optionally supervised. A bro-
ken wire in the connection with an instrument
transformer or a sensor can be detected and
an alarm can be activated.
Protection
REF 542plus offers a wide range of functions
for protection. As previously mentioned, a
wide range of protection schemes for the pro-
tection of several system components can be
configured. The available protection func-
tions depend on the ordered software
licenses. The licenses are Basic Low, Basic,
Multi Low, Multi, Differential and Distance.
In table 20 the corresponding provided pro-
tection functions are listed.
Current protection:
•
inrush blocking (68)
•
overcurrent instantaneous (50)
•
overcurrent definite time, 2 thresholds
(51)
•
overcurrent directional, 2 thresholds (67)
•
overcurrent IDMT (51 IDMT)
•
earth fault, 2 thresholds (51N)
•
earth fault IDMT (51 IDMT)
•
earth-fault directional, 2 thresholds (67N)
•
earth-fault directional sensitive (67S)
•
earth-fault directional sector (67NS), 10
thresholds.
Voltage protection:
•
overvoltage instantaneous (59)
•
overvoltage definite time, 2 thresholds
(59)
•
undervoltage Instantaneous (27)
•
undervoltage definite time, 2 thresholds
(27)
•
residual overvoltage, 2 thresholds (59N)
Line protection:
•
distance protection (21)
Differential protection:
•
differential protection for motors and
transformer (87)
•
restricted earth-fault for transformer
(87N)
Thermal protection:
•
for cables, motors and transformers (49)
Motor-specific protection:
•
number of starts counting (66)
•
locked rotor (51LR)
•
motor start (51MS)
•
low load (37)
•
unbalanced load (46)
Power quality mitigation:
•
power factor controller (55)
•
switching resonance protection
•
high harmonics protection
Other protections and related functions:
•
frequency protection (81), 6 thresholds
per net
•
synchro check (25)
•
fault recorder
•
autoreclosure (79)
•
directional power (32).
At most 24 protection functions can be
installed inside the REF 542plus unit. The
maximum number is anyway dependent upon
the available processing power.