6.1.6
Monitored data
PID-3701-MONITOREDDATA v3
Table 40:
LT3CPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
OPENCTIN
INTEGER
-
-
Open CT on Input : 1 for
input 1, 2 for input 2
OPENCTPH
INTEGER
-
-
Open CT in Phase : 1 for
L1, 2 for L2, 3 for L3
IDL1MAG
REAL
-
A
Magnitude of fund. freq.
differential current,
phase L1
IDL2MAG
REAL
-
A
Magnitude of fund. freq.
differential current,
phase L2
IDL3MAG
REAL
-
A
Magnitude of fund. freq.
differential current,
phase L3
IBIAS
REAL
-
A
Magnitude of the bias
current, common for L1,
L2, L3
IDNSMAG
REAL
-
A
Magnitude of the
negative sequence
differential current
NSANGLE
REAL
-
deg
Angle between local and
remote neg. seq.
currents
ICHARGE
REAL
-
A
Amount of compensated
charging current
6.1.7
Operation principle
6.1.7.1
Algorithm and logic
M13652-3 v7
The Line differential protection function evaluates measured current values from
local and remote line ends in order to distinguish between internal or external faults
or undisturbed conditions.
The local currents are fed to the IED via the analog input modules and then they
pass the analog-to-digital converter, as shown in Figure
1MRK 505 394-UEN A
Section 6
Differential protection
Line differential protection RED650 2.2 IEC
93
Technical manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Page 2: ......
Page 36: ...30...
Page 46: ...40...
Page 232: ...226...
Page 272: ...266...
Page 288: ...282...
Page 306: ...300...
Page 406: ...400...
Page 436: ...430...
Page 502: ...496...
Page 614: ...608...
Page 628: ...622...
Page 644: ...638...
Page 760: ...754...
Page 778: ...772...
Page 814: ...808...
Page 870: ...864...
Page 874: ...868...
Page 924: ...918...
Page 925: ...919...