Table 40. Wattmetric based earth-fault protection (WPWDE)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: fn
±2 Hz
Current and voltage: ±1.5 % of the set value or ±0.002 x
In Power: ±3 % of the set value or ±0.002 x Pn
Start time
1)2)
Typical 63 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode
±5.0% of the set value or ±20 ms
Suppression of harmonics
-50dB at F= n x fn, where n=2,3,4,5,…
1)
Io varied during the test. Uo = 1.0 x Un = phase to earth voltage during earth-fault in compensated or un-earthed network. The residual power value
before fault = 0.0 p.u., fn = 50 Hz, results based on statistical distribution of 1000 measurement.
2)
Includes the delay of the signal output contact.
Table 41. Wattmetric based earth-fault protection (WPWDE) main settings
Parameter
Function
Values (Range)
Step
Directional mode
WPWDE
2=Forward
3=Reverse
Current start value
WPWDE
0.010...5.000 x I
n
0.001
Voltage start value
WPWDE
0.010...1.000 x U
n
0.001
Power start value
WPWDE
0.003...1.000 x P
n
0.001
Reference power
WPWDE
0.050...1.000 x P
n
0.001
Characteristic angle
WPWDE
-179...180 deg
1
Time multiplier
WPWDE
0.05...2.00
0.01
Operating curve type
WPWDE
Definite or inverse time
Curve type: 5, 15, 20
Operate delay time
WPWDE
60...200000 ms
10
Min operate current
WPWDE
0.010...1.000 x I
n
0.001
Min operate voltage
WPWDE
0.01...1.00 x U
n
0.01
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
40
ABB
Summary of Contents for RED615 ANSI
Page 1: ...Relion 615 series Line Differential Protection and Control RED615 Product Guide...