![ABB RED615 ANSI Product Manual Download Page 26](http://html1.mh-extra.com/html/abb/red615-ansi/red615-ansi_product-manual_3366111026.webp)
Table 16. Protection communication link
Connector
Fibre type
Wave length
Max. distance
Permitted path attenuation
1)
LC
MM 62.5/125 or 50/125
μm
1300 nm
2 km
< 8 dB
LC
SM 9/125 μm
2)
1300 nm
20 km
< 8 dB
1)
Maximum allowed attenuation caused by connectors and cable altogether
2)
Use single-mode fibre with recommended minimum length of 3 m to connect RED615 to the pilot wire modem RPW600.
Table 17. IRIG-B
Description
Value
IRIG time code format
B004, B005
1)
Isolation
500V 1 min.
Modulation
Unmodulated
Logic level
TTL Level
Current consumption
2...4 mA
Power consumption
10...20 mW
1)
According to 200-04 IRIG -standard
Table 18. Degree of protection of flush-mounted IED
Description
Value
Front side
IP 54
Rear side, connection terminals
IP 20
Table 19. Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
-40...+70ºC (<16h)
1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
Transport and storage temperature range
-40...+85ºC
1)
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2)
For IEDs with an LC communication interface the maximum operating temperature is +70 ºC
Line Differential Protection and Control
1MRS756500 F
RED615
Product version: 4.0
26
ABB
Summary of Contents for RED615 ANSI
Page 1: ...Relion 615 series Line Differential Protection and Control RED615 Product Guide...
Page 64: ...64...
Page 65: ......
Page 66: ......
Page 67: ......