EXE_OP
CLOSEPOS
EXE_OP
OPENPOS
AdaptivePulse=FALSE
tOpenPulse
tOpenPulse
AdaptivePulse=TRUE
tStartMove timer
en05000099.vsd
IEC05000099 V1 EN
Figure 123:
Open command with open position indication
Error handling
Depending on the error that occurs during the command sequence the error signal will be
set with a value. Table
describes vendor specific cause values in addition to these
specified in IEC 61850-8-1 standard. The list of values of the “cause” are in order of
priority. The values are available over the IEC 61850. An output L_CAUSE on the
function block indicates the latest value of the error during the command.
Table 196:
Vendor specific cause values for Apparatus control in priority order
Apparatus control
function
Description
–22
wrongCTLModel
–23
blockedForCommand
–24
blocked-for-open-command
–25
blocked-for-close-command
–30
longOperationTime
–31
switch-not-start-moving
–32
persistent-intermediate-state
–33
switch-returned-to-initial-position
–34
switch-in-bad-state
–35
not-expected-final-position
Section 10
1MRK 511 287-UUS A
Control
270
Technical manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Page 2: ......
Page 42: ...36 ...
Page 60: ...54 ...
Page 66: ...60 ...
Page 424: ...418 ...
Page 566: ...560 ...
Page 636: ...630 ...
Page 699: ...693 ...