A typical connection is shown below in figure
IEC11000054-1-en.vsd
IEC11000054 V1 EN
Figure 127:
Tripping logic common 3-phase output SMPPTRC (94) is used for a
simple three-pole tripping application
11.1.2.2
Lock-out
This function block is provided with possibilities to initiate lock-out. The lock-out can be
set to only activate the block closing output CLLKOUT or initiate the block closing output
and also maintain the trip signal (latched trip).
The lock-out can then be manually reset after checking the primary fault by activating the
input reset Lock-Out RSTLKOUT or via the HMI.
If external conditions are required to initiate Lock-out but not initiate trip this can be
achieved by activating input SETLKOUT. The setting
AutoLock
=
Disabled
means that
the internal trip will not activate lock-out so only initiation of the input SETLKOUT will
result in lock-out. This is normally the case for overhead line protection where most faults
are transient. Unsuccessful autoreclose and back-up zone tripping can in such cases be
connected to initiate Lock-out by activating the input SETLKOUT.
11.1.2.3
Blocking of the function block
Blocking can be initiated internally by logic, or by the operator using a communication
channel. Total blockage of Tripping logic (SMPPTRC ,94) function is done by activating
the input BLOCK and can be used to block the output of SMPPTRC (94) in the event of
internal failures.
Section 11
1MRK 511 286-UUS A
Logic
270
Application manual
Summary of Contents for REC650 ANSI
Page 1: ...Relion 650 series Bay control REC650 ANSI Application manual...
Page 2: ......
Page 26: ...20...
Page 66: ...Section 3 1MRK 511 286 UUS A REC650 setting examples 60 Application manual...
Page 71: ...IED IED ANSI05000460 V2 EN 1MRK 511 286 UUS A Section 4 Analog inputs 65 Application manual...
Page 82: ...76...
Page 92: ...86...
Page 170: ...164...
Page 176: ...170...
Page 274: ...268...
Page 288: ...282...
Page 350: ...344...
Page 369: ...363...