Figure 64:
Ground fault in Non-effectively grounded systems
7.3.3.3
Direct grounded system
In direct grounded systems, an ground fault on one phase indicates a voltage collapse in
that phase. The two healthy phases will have normal phase-to-ground voltages. The
Section 7
1MRK 511 286-UUS A
Voltage protection
160
Application manual