Table 9. Electromagnetic compatibility tests
Description
Type test value
Reference
Electrostatic discharge test:
EN 61000-4-2
• Contact discharge:
4 kV
• Indirect contact discharge:
4 kV
Conducted RF Immunity test:
EN 61000-4-6
• 150 kHz...80 MHz
3 V (rms)
Radiated RF Immunity test:
EN 61000-4-3
• 80...2700 MHz
3 V/m (rms)
Fast transient disturbance tests:
EN 61000-4-4
• All ports
1 kV
Surge immunity test:
EN 61000-4-5
• AC power input ports
2 kV, line-to-earth
1 kV, line-to-line
Voltage dips and short interruptions
0 % / 1 cycle
EN 61000-4-11
40 % / 10 cycles
70 % / 25 cycles
Emission tests:
CISPR 22 (EN 55022), Class B
• Conducted
0.15...0.50 MHz
< 66 dB(µV) quasi peak
< 56 dB(µV) average
0.5...5 MHz
< 56 dB(µV) quasi peak
< 46 dB(µV) average
5...30 MHz
< 60 dB(µV) quasi peak
< 50 dB(µV) average
• Radiated
30...230 Mhz
< 35 dB(µV/m) quasi peak,
measured at 3 m distance
230...1000 MHz
< 42 dB(µV/m) quasi peak,
measured at 3 m distance
1000...3000 MHz
< 70 dB(µV/m) quasi peak,
< 50 dB(µV/m) average,
measured at 3 m distance
3000...6000 MHz
< 74 dB(µV/m) quasi peak,
< 54 dB(µV/m) average,
measured at 3 m distance
Wireless Controller
1MRS757423 A
REC601/603
Product version: 1.0
18
ABB