The equation above also implies that each individual binary output corresponds actually to one
integer, which is presented in the input ZONCONI and can be defined by:
CZ×2
6
or
ZONEx×2
x-1
, (1≤x≤6).
Refer to Table
for the description of such representations.
Table 47: Integer representations for the binary outputs of BCTZCONN
Output names
Type
Description
Corresponding integer value
in ZONCONI
When
deactivated
When
activated
ZONE1
BOOLEAN
Bay is connected to Z1
0
1
ZONE2
BOOLEAN
Bay is connected to Z2
0
2
ZONE3
BOOLEAN
Bay is connected to Z3
0
4
ZONE4
BOOLEAN
Bay is connected to Z4
0
8
ZONE5
BOOLEAN
Bay is connected to Z5
0
16
ZONE6
BOOLEAN
Bay is connected to Z6
0
32
CZ
BOOLEAN
Supervision status of the check zone
on differential zones (Valid only for
feeder bays)
0
64
Figure
shows an example how to use BCTZCONN to facilitate the recording of the zone
connection information from one bay, say feeder 01, to a disturbance recorder in ACT for any
six-zone busbar differential protection application.
IEC16000075-1-en.vsdx
IEC16000075 V1 EN-US
Figure 194: BCTZCONN connection example
13.11
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
SEMOD158419-1 v3
13.11.1
Identification
SEMOD167944-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion
with logic node representation
ITBGAPC
-
-
Section 13
1MRK 505 370-UEN D
Logic
346
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...