For a bus-coupler bay in section 1, these conditions are valid:
BBTR_OP (sect.1)
DCOPTR (A1A2)
DCOPTR (B1B2)
BBTR_OP (sect.2)
&
VP_BBTR (sect.1)
VPDCTR (A1A2)
VPDCTR (B1B2)
VP_BBTR (sect.2)
EXDU_12 (sect.1)
EXDU_DC (B1B2)
EXDU_12 (sect.2)
VP_BBTR
EXDU_12
en04000483.vsd
&
EXDU_DC (A1A2)
BBTR_OP
>1
&
IEC04000483 V1 EN-US
Figure 154: Signals to a bus-coupler bay in section 1 from any bays in each section
For a bus-coupler bay in section 2, the same conditions as above are valid by changing section
1 to section 2 and vice versa.
12.4.3.4
Signals from bus-coupler
M13553-58 v5
If the busbar is divided by bus-section disconnectors into bus-sections, the signals BC_12 from
the busbar coupler of the other busbar section must be transmitted to the own busbar coupler
if both disconnectors are closed.
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
ABC_BC
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
en04000484.vsd
IEC04000484 V1 EN-US
Figure 155: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL
Another bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:
Signal
BC12CLTR
A bus-coupler connection through the own bus-coupler exists between busbar
WA1 and WA2.
VPBC12TR
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from the bay that contains the above information.
Section 12
1MRK 505 370-UEN D
Control
308
Busbar protection REB670
Application manual
Summary of Contents for REB670 Series
Page 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 64: ...58 ...
Page 226: ...220 ...
Page 244: ...238 ...
Page 358: ...352 ...
Page 392: ...386 ...
Page 398: ...392 ...
Page 436: ...430 ...
Page 454: ...448 ...
Page 466: ...460 ...
Page 474: ...468 ...
Page 475: ...469 ...