Accepted originator categories for PSTO
If the requested command is accepted by the authority control, the value will
change. Otherwise the attribute
blocked-by-switching-hierarchy
is set in the
cause
signal. If the PSTO value is changed during a command, then the command is
aborted.
The accepted originator categories for each PSTO value are shown in
.
Table 18:
Accepted originator categories for each PSTO
Permitted Source To Operate
Originator (orCat)
0 = Off
4,5,6
1 = Local
1,4,5,6
2 = Remote
2,3,4,5,6
3 = Faulty
4,5,6
4 = Not in use
4,5,6
5 = All
1,2,3,4,5,6
6 = Station
2,4,5,6
7 = Remote
3,4,5,6
PSTO = All, then it is no priority between operator places. All operator places are
allowed to operate.
According to IEC 61850 standard the
orCat
attribute in originator category are
defined in
Table 19:
orCat attribute according to IE C61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process
10.1.2
Bay control QCBAY
M16595-3 v10
The Bay control (QCBAY) is used to handle the selection of the operator place per
bay. The function gives permission to operate from two main types of locations
either from Remote (for example, control centre or station HMI) or from Local
1MRK 505 388-UEN B
Section 10
Control
Busbar protection REB650 2.2 IEC
155
Application manual
Summary of Contents for REB650
Page 1: ...RELION 650 SERIES Busbar protection REB650 Version 2 2 Application manual...
Page 2: ......
Page 18: ...12...
Page 28: ...22...
Page 38: ...32...
Page 78: ...72...
Page 96: ...90...
Page 136: ...130...
Page 150: ...144...
Page 156: ...150...
Page 232: ...226...
Page 278: ...272...
Page 298: ...292...
Page 310: ...304...
Page 320: ...314...
Page 321: ...315...