Chapter 3 – Installation
RDIO-01 User’s manual
3-5
Wiring
0.5 to 1.5 mm
2
twisted pair unshielded cable with an
appropriate voltage rating should be used for digital
signals.
WARNING!
According to international standards,
applying voltages below 50 V (DC or AC) and above
150 V (AC or DC) simultaneously to the digital inputs
and/or outputs of the RDIO-01 is not allowed.
Additionally, only voltages of the same nominal level
should be applied simultaneously to digital inputs DI2
and DI3 due to reduced isolation voltage.
Note:
Do not route signal cables parallel to power
cables.
Digital input wiring
examples
RDIO
DIxA
DIxB
110…230 V AC ±10%
RDIO
DIxA
DIxB
24…250 V DC
(polarity unimportant)