background image

In addition to what is explained in this guide, the safety and installation 

information provided in the technical manual must be read and followed.

The technical documentation and the interface and management software for 

the product are available at the website.

Quick installation guide

PVI-3.0-3.6-3.8-4.2-TL-OUTD-S-US (-A)

Solar inverters

1.

Labels and warnings

3.

W

all mounting

Installation location

2.

Switchbox wiring

4.

DC input connections 

5.

EN

165mm

188mm

80mm

DC conduit entry plastic threaded plugs 

size 1”, 1-1/4” 

H

Cover screws (4)

B

AC conduit entry plastic threaded plugs 

size 1”, 1-1/4” 

J

AC grid output terminals, NOTE 1

C

DC Disconnect Switch

K

AC main ground, NOTE 2

D

Signal cable opening with plastic threaded 

plug, 1/2” trade size

L

Array PE ground, NOTE 1

E

AC cable opening with plastic threaded plug; size 

1”, 1-1/4” 

M

AFD board (

-A only

)

F

DC cable opening with plastic threaded 

plug; size 1”, 1-1/4” 

MPPT1 and MPPT2 DC array input, NOTE 1

Components included in mounting kit XAK.00060.0

1 Wall bracket shown at right - 833G7424400-G

1  Hardware bag containing:

4 - 6.3 x 70mm screws, washers, and- S x 10 anchors 

1 - 6 x 10mm machine screw    1 - 6mm flat washer

1 - Red cable AWG10 - 9153G038600

1 - Black cable AWG10 - 9153G038700

1 - Torx 20 wrench 

81510000077

2 - Terminal connectors 

82000006439-G 

• 

Using the mounting bracket as a template, locate and mark the 

desired mounting location.

• 

Using the four screws provided, level and mount the bracket to 

the surface using mounting holes 

B

.  

• 

Two additional screws can be used in 

A

 if necessary. 

• 

Orient the bracket such that the hooks in position 

C

 face 

outward and upward.

• 

Hang the inverter on the mounted bracket by lifting the unit up 

and over the mounting plate. 

• 

Guide the inverter and switchbox brackets engaging the 

brackets 

C-D

 and 

E-F

 on the back of the inverter.

• 

Secure chassis bottom using the machine screw and washer 

provided through center hole 

H

 and engaging in the bracket 

G

.  

• 

Add additional screws as necessary through bottom flange 

securing to mounting surface.

M

Switch and wiring box with AFD board mounted on 

din rail  -A model only (label M) 

Switch and wiring box internal view

NOTE 1:

 DC array wiring and ground terminals are spring pressure type and accommodate a wire size 

range of 16-6 AWG. AC output terminals are spring pressure type and accommodate a wire size range of 

14-4 AWG.  

NOTE 2:

 AC ground terminals are spring pressure type and accept 16-4 AWG wire.

The switch disconnects the DC current from the PV panels in the “OFF” position. The inverter will stop producing power, but DOES NOT disconnect 

the AC from the grid.  To prevent electrocution hazards, all the connection operations must be carried out with the external AC disconnect switch 

downstream of the inverter (grid side) open and locked out.

Switch and wiring box external view

The maximum allowable input short circuit current limit of the PV array for each MPPT input channel is 20Adc for 3.6kW, 3.8kW and 4.2kW inverters; 12.5Adc for 

the 3.0kW.  Array equipment grounding must be installed per the requirements of the NEC and is the responsibility of the installer.  
The transformerless design requires that the PV array to be floating with respect to ground per NEC 690.35.

• 

The inverter can be configured with two independent maximum power point tracking (MPPT) channels or as a single channel with one MPPT 

by paralleling the two channels. 

• 

Parallel two inputs when the current from PV array exceeds 20 Adc for the PVI-3.6/3.8/4.2 or 12.5 A for the PVI-3.0, or array power exceeds 

limit for single channel (section 

13

).

• 

Switch S1, located on the inverter connection board, is used to select parallel (

PAR

) or independent (

IND

) input mode

• 

The default position of switch S1 is set in the IND mode (DOWN).

• 

To access the switchbox wiring and Switch S1, loosen the four captive screws on the inverter cover and wiring box cover using the Torx 

wrench provided.  

Before removing front covers, DC switch must be in the OFF position.

• 

When complete

re-install the front covers and tighten the cover screws with at least 1.5Nm (13.2 in-lbs) torque.

• 

Use DC knockouts (section 

4

) to connect raceway from the PV array conduits to the DC array. 

Independent mode configuration 

Independent mode configuration - single string

• 

Connect array to String 1 and String 2 input positions shown below, running 

separate wires for POS and NEG for each array. 

• 

Up to four strings can be connected in the INDEPENDENT mode.

• 

To connect four strings, String 3 and String 4 are connected in addition to 1 

and 2, running separate wires for POS and NEG for each array.

• 

Confirm switch S1 is set in the IND position (DOWN).

The inverter can be operated in the Independent mode from a single array by 

connecting to only one input channel. 

• 

Connect array to one input channell (String 1 input shown), running separate 

wires for POS and NEG.

• 

Short circuit the unused input not connected to a PV array (input 2 shown) 

using the black 10AWG jumper wire provided.

INDEPENDENT configuration

INDEPENDENT configuration - single string

Parallel mode configuration -S version without AFD

Parallel mode configuration -S version with AFD (-A)

• 

Connect array to String 1 and String 2 input positions shown below, running 

separate wires for POS and NEG for each array. 

• 

For versions without AFD, 

parallel the two MPPT inputs of terminal  

–IN1/–IN2 and +IN1/+IN2 

in the switchbox

, using the two #10 AWG jumper 

wires provided, 1 black and 1 red, 

• 

Connect the input as shown below.

• 

Confirm switch S1 is set in the PAR position (UP) 

• 

When Arc Fault Detection (AFD) is installed, the paralleling must be 

done on the main board inside the inverter.

• 

Connect array to String 1 and String 2 input positions 

in the switchbox 

as 

shown at left, running separate wires for POS and NEG for each array. 

• 

For -A versions only, 

parallel the two MPPT inputs of –IN1 and –IN2 

and +IN1 and +IN2 

in the inverter,

 using the two #10 AWG jumper wires 

provided, 1 black and 1 red.  Connect the input as shown below and tighten 

with 13in-lbs torque.

• 

Confirm switch S1 is set in the PAR position (UP) 

PARALLEL configuration - models without AFD 

PARALLEL configuration - models with AFD (-A) 

-IN1

-IN2

+IN1

+IN2

This inverter has been tested and found to comply with the limits for a Class B digital device, pursuant 

to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against 

harmful interference in a residential installation.    This equipment generates, uses and can radiate 

radio frequency energy and, if not installed and used in accordance with the instructions, may 

cause harmful interference to radio communications. However, there is no guarantee that 

interference will not occur in a particular installation.  If this equipment does cause harmful 

interference to radio or television reception, which can be determined by turning the equipment off 

and on, the user is encouraged to try to correct the interference by one or more of the following 

measures:  a) Reorient or relocate the receiving antenna; b) Increase the separation between the 

equipment and receiver; c) Connect the equipment into an outlet on a circuit different from that 

to which the receiver is connected; d) Consult the dealer or an experienced radio/TV technician 

for help.

• 

The PV source conductors must be Listed PV wire per NEC 690.35. PV output conductors shall consist of sheathed (jacketed) multi-conductor cables or installed in 

an approved raceway and must be isolated from the enclosure and system grounding, as required by NEC 690.35 and is the responsibility of the installer.

• 

To reduce the risk of fire, connect only to a circuit provided with 15A, 20A, or 25A maximum branch circuit overcurrent protection in accordance with the NEC (ANSI/

NFPA 70).  The inverter must be connected only to a dedicated branch circuit provided with the maximum branch OCPD listed in the technical data table, section 

13

• 

All models listed in the technical data table, section 13, have an integrated DC disconnect switch rated 600V/25A per contact. 

• 

Maximum array DC voltage input to each MPPT circuit is 600 Vdc under any condition.

 To STRING 1

 To STRING 1

 To STRING 2

 To STRING 4

(OPTIONAL)

 To STRING 3

(OPTIONAL)

 To STRING 1

To STRING 2

Jumpers for PARALLEL 

input mode -S version only

Short circuit INPUT 2

with black jumper

Jumpers for PARALLEL 

input mode -A version only

 6

 in

  8

 in

 6 in

  6 in

UNO

Direct sunlight use caution

Air flow restricted use caution

Environmental checks 

- See technical data table, section 

13

, to check environmental parameters. 

• 

Maximum operational ambient air temperature must be considered when choosing location. Installing the inverter where 

operating temperatures exceed specifications will result in power derating. It is recommended the inverter be installed 

within specified temperature range.

• 

Exposure to direct sunlight will increase operational temperature of inverter and may cause output power limiting. It 

is recommended to use a sun shade to minimize direct sunlight when ambient air temperature around unit exceeds 

104°F/40°C.

• 

Due to acoustical noise (about 50dBA at 1 m) from inverter, do not install in rooms where prolonged presence of people 

or animals is expected. 

Installation position - 

• 

Install on a wall or strong structure capable of bearing weight.

• 

Install vertically with a maximum incline of +/- 5°.

• 

Maintain minimum clearance measurements shown.

• 

Ensure sufficient working area in front of inverter for 

wiring box access.

• 

Choose a location that allows unobstructed airflow 

around inverter.

• 

Position multiple inverters side-by-side, maintaining 

minimum clearances. 

• 

Multiple inverters can 

also be placed in staggered 

arrangement.

• 

Minimum clearances for 

staggered arrangements 

include width of inverter plus 

additional allowances for 

inverters arranged above or 

below.

Side-by-side arrangement

Staggered arrangement

6”

6”

25”

25”

25”

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS-KEEP IN SAFE PLACE!

The installer must read this document in its entirety before installing or commissioning this equipment.

The labels on the inverter carry the markings, main technical data and identification of the equipment and manufacturer.  The technical data shown in this quick 

installation guide does not replace that shown on the labels attached to the equipment.

UL 1741

CSA-C22.2 No. 107.1-01

C

US

®

Country of Origin Italy

www.abb.com/solar

SOLAR UTILITY INTERACTIVE

TRANSFORMERLESS INVERTER

MODEL: PVI-3.0-OUTD-S-US

This device complies with Part 15 of the FCC Rules. Operation is subject to the

following two

 (2) this device must accept any interference received, including interference that may 

 cause undesidered operation.

Nominal Input Operating Voltage
Max. Input Voltage
Range of Input Operating Voltage
Range of Input Voltage @Full Power
Max. Input Current

Max. Input Short Circuit Current (P.V. Panels)

DC RATING

Nominal Output Voltage
Operating Voltage Range
Nominal Output Frequency
Operating Frequency Range
Output Power Factor
Max. Output Current

AC RATING

Max. Continuous Output Power
Max. Output Overcurrent Protection

2 x 10 A

2 x 12.5 A

360 V

600 V

90 - 580 V

200 - 530 V

60 Hz (factory preset)

59.3 ( ) - 60.5 ( ) Hz

1

2

>0.995

12 A / 14.5 A / 14.5 A (rms)

277 V~ / 240 V~ / 208 V~ 1Ø

15 A / 20 A / 20 A

3000 W @ 55°C amb.

244-304 V~/211-264 V~/183-228 V~

DC Ground Fault Detector/Interrupter is Provided

Operating Ambient Temperature: -25 to +60 °C (-13 to +140 °F), with Output Power Derating
Type of Enclosure: NEMA 4X

For more details about product specifications refer to the Instruction Manual

(

1

):

2

Adjustable from 57.0 Hz to 59.8 Hz

Adjustable from 60.2 Hz to 63.0 Hz

( ):

 

conditions: (1) this device may not cause harmful interference, and

1

2

3

4

5

7

8

6

Product nameplate labels and descriptions

Certification

AC output ratings

2

Product origin

6

Environmental data

3

Model type and number

7

Protection

4

DC input ratings

8

Adjustable parameters

1

5

Main symbols used in the guide and on the products

UL 1741; CSA-C22.2 No. 107.1-01

General warning - Important safety 

information

Hazardous voltage

Hot surfaces

System earth conductor  

(main grounding protective earth, PE) 

ø

Phase

Grounding (earth)

  

Direct and alternating currents, 

respectively