PVI-3.0-3.6-3.8-4.2-TL Quick Installation Guide
BCM.00161.1_AA
© Copyright 2014 ABB. All Rights Reserved.
Specifications subject to change without notice.
6.
AC output connections
AC output overcurrent protection is not provided with the inverter; it is the responsibility of the end user to provide overcurrent protection for the AC output circuit.
To prevent electrocution hazards, all the connection operations must be carried out with the external AC disconnect switch downstream of the inverter (grid side) open
and locked out.
Size conductors per NEC Article 310; Use 90°C copper wire only; terminal
block accommodates wire size range of 14-4 AWG.
The AC grid wiring is connected through the
inverter switchbox.
•
Run an approved raceway between inverter
and external AC disconnect switch.
•
Make conduit entry through openings
B
or
E
shown in section
4
.
•
Connect AC wiring to switch box terminal
block
J
and the main AC ground cable to
switchbox terminal block
K
shown at left.
•
Table at right shows AC wiring connections
based on the AC grid type, (also found on a label
in the switchbox).
•
connect wiring to the numbered terminals
based on selected grid type.
The default 240V-SPLIT-PHASE connection requires the grid Neutral to be connected for proper operation. Before connecting the inverter to the grid, the grid type must
be selected if it differs from the default 240V-SPLIT-PHASE setting. See Section 10 for instructions to change the default. If several inverters are installed to a three-phase
AC GRID, always distribute the inverters between the phases in order to reduce power imbalance between the phases.
7.
Communication wiring
Wiring for the RS-485 communication system and hardwired control options are routed through the switchbox (section
4
) and into the main inverter chassis for termination. Alarm and
monitoring connections are shown as items
Q
and
R
.
Refer to the technical manual online for connections to ALARM (Q) and Rem (remote control).
The WIND terminals (±WT ) are not isolated and can have hazardous voltages pres-
ent. These terminals must not be utilized for any purpose in a PV installation (use
with wind models only).
To connect the communication wiring, it is necessary to open the inverter cover and access the
communication connections located on the main board.
•
T o remove the front cover of the inverter compartment, loosen the four captive screws
indicated using the Torx screwdriver provided.
•
When connection operations are complete, re-install the front covers and tighten the
cover screws with at least 1.5Nm (13.2 in-lbs) torque to ensure proper waterproof
sealing.
The RS-485 communication line connects the inverter to the monitoring devices and may be
“daisy-chained” (in-out) among multiple inverters. The RS-485 connecting cables can use both the
terminal connections
R
, as well as the RJ45 connectors
S
, to connect to the dedicated port.
If a daisy chain connection is required for AFD installed inverters (-A models) use standard
multiconductor RS-485 cable and connect the three RS-485 leads (-RTN, +T/R,-T/R)
USING ONLY THE MATING CONNECTORS.
Do not use RJ45 connectors with AFD installations.
RS-485 connectors
(R)
•
If terminal blocks are used, signals RTN, +T/R and –T/R have to be cabled.
•
Use a cable designed for use with RS-485 communications.
•
Locate mating connectors (provided in hardware bag) for the terminal block.
•
Connect the three (-RTN, +T/R, -T/R) to the mating connector corresponding points.
•
Attach mating connector to line up with correct signals on either upper or lower terminal
rows (two parallel terminals rows are on the terminal block and two mating connectors
are included).
RJ45 connectors
(S)
•
RJ45 connectors (1) and (2) available for the RS-485 communication are equivalent to
each other and can be used interchangeably for input or output of the line to create the
daisy chain connection of the inverters.
•
Do not use RJ45 connectors with AFD installations.
Daisy chain connection
•
Recommended length of total communication cable line for all inverters in
the system is 1,000 meters [1094 yards] or less.
•
Depending on type of computer used, cable line adaptor can be RS-485-
RS232 or RS-485-USB.
Termination switch
(S2)
•
On the last inverter in a daisy chain, or on a single inverter, activate
termination resistance by moving switch S2 down into the ON position.
•
All other inverters in daisy chain will have the switch up in the OFF
position.
Addressing each inverter
•
Default setting for RS-485 address is 2 and termination switch in OFF
position.
•
When multiple inverters are connected in a daisy chain, it is necessary to
assign a different RS-485 address to each unit.
See
section 10
for instruction on using the display to configure settings.
Refer to the technical manual online for connection of alarm wiring (
Q)
and Rem (remote control).
R
Q
S
T
P
P
Input Mode Selector Switch S1
Q
External alarm Out Terminals
R
RS-485 Terminal Block*
S
RS-485 RJ45 Connector**
T
RS-485 Line Termination Resistor Switch S2
* REM-Remote control not available for -A model; teR is not
accessible with AFD
** DO NOT CONNECT pin #4 when cabling units with AFD installed.
S2=OFF
S2=OFF
S2=ON
DAISY CHAIN CONNECTION
•
LEDs indicate operating state of the inverter.
•
Operating parameters of the equipment are displayed in two line LCD.
•
Controls on keypad are used to review data on the LCD and access
data logged internally.
Text in LCD
consists of 2 lines with 16 characters per line.
•
Press the ENTER key to stop menu scrolling.
•
Press the ESC key to access the three MAIN MENUS:
STATISTICS - SETTINGS - INFO
LED INDICATORS
PROGRAMMING
CONTROLS
TWO LINE
LCD DISPLAY
TECHNICAL DATA
VALUES
PVI-3.0-OUTD-US
PVI-3.6-OUTD-US
PVI-3.8-OUTD-US
PVI-4.2-OUTD-US
Nominal Output Power
W
3000
3600
3300
3800
4200
Maximum Output Power
W
3000
3300
2
3300
2
3600
4000
2
4000
2
3300
4200
2
4200
2
4200
4600
2
4600
2
Rated Grid AC Voltage
V
208
240
277
208
240
277
208
240
277
208
240
277
Number of Independent MPPT Channels
2
2
2
2
Maximum Usable Power for Each
Channel
W
2000
3000
3000
3000
Absolute Maximum Voltage (Vmax)
V
600
Start- Up Voltage (Vstart)
V
200 (adj. 120-350 )
Full Power MPPT Voltage Range
V
160-530
120-530
140-530
140-530
Operating MPPT Voltage Range
V
0.7xVstart-580 (>= 90V)
Maximum Current (Idcmax) for both
MPPT in Parallel
A
20
32
32
32
Maximum Usable Current per Channel
A
10
16
16
16
Maximum Short Circuit Current Limit
per Channel
A
12.5
20.0
20.0
20.0
#of Wire Landing Terminals Per Channel
2 pairs
Array Wiring Termination
Terminal block, Pressure Clamp, AWG10-AWG4
Grid Connection Type
1Ø/2W
Split-
Ø/3W
1Ø/2W 1Ø/2W
Split-
Ø/3W
1Ø/2W 1Ø/2W
Split-
Ø/3W
1Ø/2W 1Ø/2W
Split-
Ø/3W
1Ø/2W
AdjustableVoltage Range (Vmin-Vmax)
V
183-
228
211-
264
244-
304
183-
228
211-
264
244-
304
183-
228
211-
264
244-
304
183-
228
211-
264
244-
304
Grid Frequency
Hz
60
Adjustable Grid Frequency Range
Hz
57-63
Maximum Current (Iacmax)
A
RMS
14.5
14.5
12.0
17.2
16.0
16.0
16.0
16.0
16.0
20.0
20.0
20.0
Power Factor
> 0.995
Total Harmonic Distortion At Rated
Power
%
< 2
Grid Wiring Termination Type
Terminal block, Pressure Clamp AWG10 - AWG4
Reverse Polarity Protection
Yes
Over-Voltage Protection Type
Varistor, 2 for each channel
PV Array Ground Fault Detection
Pre start-up Riso and dynamic GFDI (Requires Floating Arrays)
Anti-Islanding Protection
Meets UL 1741/IEE1547 requirements
External AC OCPD Rating
A
RMS
20
20
15
25
20
20
20
20
20
25
25
25
Over-Voltage Protection Type
Varistor, 2 (L
1
- L
2
/ L
1
- G)
User-Interface
16 characters x 2 lines LCD display
Remote Monitoring (1xRS485 incl.)
AURORA-UNIVERSAL (opt.)
Wired Local Monitoring (1xRS485 incl.)
PVI-USB-RS485_232 (opt.), PVI-DESKTOP (opt.)
Wireless Local Monitoring
PVI-DESKTOP (opt.) with PVI-RADIOMODULE (opt.)
Ambient Air Operating Temp. Range
°F (°C)
-13 to +140 (-25 to +60) with derating above 122 (50)
Ambient Air Storage Temperature Range
°F (°C)
-40 to 176 (-40 to +80)
Relative Humidity
% RH
0-100 condensing
Acoustic Noise Emission Level
db (A)
@1m
< 50
Max Operating Altitude without Derating
ft(m)
6560 (2000)
Enclosure rating
NEMA 4X
Cooling
Natural Convection
Dimensions (H x W x D)
in (mm)
33.8 x 12.8 x 8.7 (859 x 325 x 222)
Weight
lb (kg)
< 47.3 (21.3)
Shipping Weight
lb (kg)
< 60 (27.0)
Mounting System
Wall bracket
Conduit Connections
3
Trade size KOs: (2ea x 1/2”) and (2ea x 1-1/4”, 3 places side, front, rear)Side: (2) plugged 3/4” openings, (2)
Concentric EKOs 3/4”, 1”, Back: (4) Concentric EKOs 3/4”, 1”
DC Switch Rating (Per Contact)
A/V
25 / 600
Isolation Level
Transformerless (Floating Array)
Safety and EMC Standard
UL 1741, IEE1547, IEE1547.1, CSA - C22.2 N. 107.1-01, UL1998 UL1699B, FCC Part 15 Class B
Safety Approval
c
CSA
us
Standard Warranty
years
10
Extended Warranty
years
15 & 20
Standard - With DC Switch and Wiring Box
PVI-3.0-OUTD-S-US
PVI-3.6-OUTD-S-US
PVI-3.8-OUTD-S-US
PVI-4.2-OUTD-S-US
With DC Switch, Wiring box and AFD Interrupter
PVI-3.0-OUTD-S-US-A
PVI-3.6-OUTD-S-US-A
PVI-3.8-OUTD-S-US-A
PVI-4.2-OUTD-S-US-A
*All data is subject to change without notice
When multiple units have been connected in a daisy chain, the individual address will need to be assigned
prior to grid connection
using the display menu. The grid default type,
240V Split Phase, can also be changed
prior to grid connection
using the display menu.
With only the array connected, set the inverter’s DC disconnect switch to ON. GREEN POWER LED will flash and YELLOW ALARM LED will be steady. The LCD will read
“Missing Grid”
. Press ESC to open the menus. Use the DOWN key to scroll to
Settings
, and press ENTER.
The Settings menu requires an access password.
Upon selecting
SETTINGS
the password screen will display; the default password is
0000
.
Pressing ENTER four times loads four zeroes on the display and opens the submenu.
The LCD has two visible text lines and the UP and DOWN control keys are used to scroll through the menu items. An arrow on the left side of the display highlights the current selection.
Move the arrow UP or DOWN to the desired selection and press ENTER to access the associated submenu (section
8
). To return to the preceding menu, press the ESC key.
Address
and
Set Vgrid
are described below for use in installation. Complete descriptions of the submenus can be found in the full manual on the website.
Address:
In the
SETTINGS
menu, scroll to
Address
and press ENTER to open the submenu. Address values are
assigned manually using any value in the range 2 to 64. Press the UP and DOWN keys to scroll through numbers
and ENTER to select. Auto address = 1 and can be used only once; default address is set at 2.
Set Vgrid:
In the SETTINGS menu, scroll DOWN to Set Vgrid and press ENTER to open the submenu. To
choose a grid connection different from the 240V Split-phase default, use the UP or DOWN key to move the
arrow to the desired selection and press ENTER. A second display screen will open; press ENTER to confirm
selection or ESC to cancel.
Upon completion turn the DC Disconnect switch OFF to save changes.
The procedure for START-UP is as follows:
•
Set the inverter’s DC disconnect switch to ON.
•
Set the external AC disconnect switch to the inverter to ON.
Once both disconnects are closed, the inverter starts the grid connection sequence.
While the system checks for grid connection (Missing Grid) to be established, the ALARM LED turns steady YELLOW
and the POWER LED flashes GREEN.
When waiting for sunlight (Waiting Sun) the POWER LED turns steady GREEN. As soon as conditions are met, the
inverter is connected to the grid.
For –A versions ONLY
, the display shows the AFD board self-test running and results upon connection. If the self-test
results are OK, the inverter will continue to Next connections.
If a potential problem on the AFD board is detected, the self-test will result in error.
Refer to section
12
below to clear the error and restart the self-test.
All versions
will display the following screens during connection:
Time (seconds) remaining to complete the output voltage and
frequency values check, and whether the values are within
range.
A final display screen confirms RISO measurement.
If all items described above test OK, the inverter is connected to the grid and displays the message,
“Inverter OK”
,
along with the date and time. If there is not sufficient sunlight to connect to the grid, the unit will repeat the connection procedure
until all the parameters controlling connection to the grid (voltage and frequency, confirmation of no ground fault) are within
range. During this procedure, the green LED flashes ON and OFF.
Clock malfunctioning, or other non-function related faults that do not interfere with operation, may also be shown instead of the date and time.
Missing Grid . . .
Waiting Sun . . . .
Test Arc Sensor
OK
12.
AFD (arc fault detection)
An autotest circuit is included in the module design of the DC ARC FAULT CIRCUIT INTERRUPTER (AFCI) solution. The AFCI performs a self-test when the system is started, (ie
every morning when sunlight is sufficient for connection). The inverter display area shows the results of the self-test:
•
If the self-test results are OK, the inverter will continue to AC grid connection.
•
If a potential problem on the AFD board is detected, the self-test will result in error.
Press and hold the ESC key for three seconds to clear the error and start the restart self-test. If self-test results are OK, the inverter will re-connect
to the AC grid. If the DC arc fault is still present, the self test will result in error E053.
Refer to the technical manual online for possible solutions.
•
During normal operation the input current is continually measured and analyzed.
•
If a DC arc fault is detected, the inverter is disconnected from the AC grid and error E050 will be displayed.
Refer to the technical manual online for possible solutions.
The AF self-test can be manually started anytime using the following procedure:
1. Turn off the inverter (switching off both DC and AC switches) and,
2. Turn on both the DC and AC switches waiting for display communication of self-test result.
Contact us
www.abb.com/solarinverters
POWER LED
GREEN:
On if the inverter is working correctly. Flashes when checking the grid or if there is insufficient sunlight.
ALARM
YELLOW
: The inverter has detected an anomaly. Anomaly is shown on the display
GFI
RED:
Ground fault on the DC side of the PV array. Error is shown on the display.
ESC
Used to access the main menu, go back to the previous menu, or go back to the previous digit to be edited.
UP
Used to scroll up the menu options or shift the numerical scale in ascending order.
DOWN
Used to scroll down the menu options or shift the numerical scale in descending order.
ENTER
Used to confirm an action, access submenu for selected option (indicated by
>
arrow symbol) or switch to next digit to be edited.
To adjust frequency and disconnect times to meet local utility requirements, modifications are made using the Aurora Manager-TL software. The software, with
instructions to download and install on a PC, can be found on the website
Prior to connecting to the grid, with the inverter’s DC disconnect switch set to ON
, a computer, with Aurora Manager-TL software installed, should
be connected to the inverter via an RS-485-USB adapter (not included). The USB driver files and instructions for installation can be found on the website.
PC-inverter connection cable required is standard USB 2.0 cable, terminals type A and B.
After frequency and disconnect time values have been adjusted, turn DC power OFF and ON to save new data. Changes to parameters must be
made to meet the requirements of the local utility. Entry of improper values could cause inverter to shut down.
Cond.
Simulated utility source
Max.time (sec) at 60Hz
a
before cessation of current to
the simulated utility
Voltage (V)
Frequency (Hz)
A
<0.50 V
nor
b
Rated (60Hz)
0.16 (Fixed)
B
0.50 V
nor
b
≤ V < 0.88 V
nor
(Adjustable)
Rated (60Hz)
2 (Fixed)
C
1.10 V
nor
b
< V<1.20 V
nor
(*) (Adjustable)
Rated (60Hz)
1 (Fixed)
D
1.20V
nor
≤ V (*)
Rated (60Hz)
0.16 (Fixed)
E
Rated
f > 60.5 Hz (Default) (Adj. 60.2 to 63.0 Hz)
0.16 (Default) (Adj. 0.16 to 300 sec)
F
Rated
f < 59.3 Hz (Default) (Adj. 59.8 to 57.0 Hz)
0.16 (Default) Adj. 0.16 to 300 sec)
G
Rated
f< 57.0 Hz
0.16 (Fixed)
H
Rated
f > 63.0 Hz
0.16 (Fixed)
9.
Frequency and disconnect parameters
The
Statistics
,
Settings
and
Info
menus can be accessed with just the array connected. Some parameters (e.g. current, voltage, power, partial energy,
lifetime energy etc.) are available only after grid connection.
Based on individual installations, the following parameters may need to be configured
prior to initial grid connection:
•
The RS-485 bus address for daisy chain (section
10
),
•
AC grid type if different from default (section
10
),
•
Adjustments to default frequency and disconnection time (section
9
).
Complete descriptions of the data available on the display menus can be found in the full manual on the website.
>Address
Display settings
Address
>2
0***
Test Arc Sensor
OK
Arc Self Test
E053
Arc Fault
E050
Arc Self Test
E053
Initializing . . .
Please wait
Meas. RISO . . .
In range
Inverter OK
Mon 03 Jan 11:00
Fgrid
50.17Hz
In range
Vgrid
223.8V
In range
Next connections
2 secs
Alarm Message
>Set Vgrid
240V Split Ph
Vnom = 240V