Functions
Chapter 10
139
1SFC132003M0201
10:15 Start ramp range
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Start Range
The time of the start ramp is settable up to 30 seconds as
default, but if required the range could be extended up to 120
seconds by this parameter.
A too long ramp time will increase the risk of tripping the
overload protection.
10:16 Stop ramp range
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Stop Range
The time for the stop ramp is settable up to 30 seconds as
default, but if required the range could be extended up to 120
seconds by this parameter.
Parameter
text
Default value Setting range
Description
Start Range 1-30 s
1-30 s, 1-120 s
Selectable
range for start
ramp
Parameter
text
Default value Setting range
Description
Stop Range 0-30 s
0-30 s, 0-120 s
Selectable range
for stop ramp
Summary of Contents for PST30
Page 2: ...This manual belongs to...
Page 4: ......
Page 8: ...Chapter 8 1SFC132003M0201 Notes...
Page 10: ...Introduction 10 1SFC132003M0201...
Page 14: ...Introduction Chapter 1 14 1SFC132003M0201...
Page 16: ...Quickstart 16 1SFC132003M0201...
Page 20: ...Description 20 1SFC132003M0201...
Page 34: ...Description Chapter 3 34 1SFC132003M0201...
Page 36: ...Mounting 36 1SFC132003M0201...
Page 40: ...Mounting Chapter 4 40 1SFC132003M0201...
Page 42: ...Connection 42 1SFC132003M0201...
Page 60: ...Connection Chapter 5 60 1SFC132003M0201...
Page 62: ...Human Machine Interface HMI 62 1SFC132003M0201...
Page 74: ...Human Machine Interface HMI Chapter 6 74 1SFC132003M0201...
Page 76: ...Setting and configuration 76 1SFC132003M0201...
Page 120: ...Fieldbus communication option 120 1SFC132003M0201...
Page 124: ...Maintenance 124 1SFC132003M0201...
Page 126: ...Maintenance Chapter 9 126 1SFC132003M0201...
Page 130: ...Chapter 130 1SFC132003M0201...
Page 178: ...Trouble shooting 178 1SFC132003M0201...
Page 188: ...Trouble shooting Chapter 11 188 1SFC132003M0201...
Page 190: ...Diagrams 190 1SFC132003M0201...
Page 199: ......