Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
19
Chapter 3
General data
Rated insulation voltage, Ui
600 V
Rated operational voltage, Ue
208-600 V 50 / 60 Hz
Rated control supply voltage, Us
100 - 250 V 50 / 60 Hz
Voltage tolerance
+10% to -15%
Frequency tolerance
± 5%
Rated impulse withstand voltage
6 kV operational circuit
/ 4 kV control supply circuit
Number of controlled phases
2
Inputs
Start, stop, reset
Analog out
4-20 mA
Cooling system
Fan
Rated duty
Uninterrupted
EMC
IEC 60947-4-2 Class A
1
Lloyds Register (2002)
Recommended fuse
Supply circuit
6A Delayed
MCB use characteristics
Communication protocols
DeviceNet/Profibus/
Modbus/CANopen
1
This product has been designed for class A equipment. Use of the product in domestic
environments may cause radio interference, in which case the user may be required to
employ additional mitigation methods.
3.7 Technical data
3.7.1 General
Table 3.2
3.7.2 Weights
Table 3.3
Type
Weight in kg
Weight in lbs
PSE18...60
2.4
5.3
PSE72...105
2.5
5.5
PSE142...170
4.2
9.2
PSE210
12.4
27.3
PSE250...370
13.9
30.6