Program features 29
Settings
String monitoring
In the -SX inverter model each individual string current is measured. The measurements
are is used to detect reverse string current, blown fuses and deviation in the measured
string currents. In the -S inverter model only the total reverse string current can be
detected.
Reverse input current detection
If reverse current is detected in the total input current, a fault is activated after a short
delay. The threshold value is initially set with parameter
so that the inverter recognizes the reverse current. Reverse input current detection is
enabled/disabled with parameter
Reverse input current detection
. Reverse current
detection is enabled by default.
Settings
Reverse input current detection
Reverse string current detection (-SX model)
If reverse current is detected in one of the connected strings, a warning is indicated. The
threshold value is initially set in parameter
, so that it
recognizes the reverse current direction. Reverse current detection is enabled with
parameter
Reverse string current detection
Settings
Reverse string current detection
Reverse string current threshold
Blown fuse detection (-SX model)
In the -SX model a warning is indicated to the user in case of a blown fuse. The blown fuse
detection is enabled with parameter
. Blown fuse is detected if
the string current is around 0.0 A in an activated string and the average string current is
greater than
Settings
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...