Parameters 79
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
174 String monitor
174.02
String monitor action
Selects how the inverter should react when a
deviation is detected in the string currents.
Warning
No
Any deviations are ignored.
0
Warning
A warning is indicated.
1
Fault
A fault event occurs and the inverter trips.
2
174.11
Input connection status
Sets the connection status of each string.
0b00000000
String 1
String 1 is configured.
0
...
...
...
String 8
String 8 is configured.
7
Reserved
8...15
174.12
Reverse string current
detection
Enables reverse current detection.
Enable
Disable
0
Enable
1
174.13
Reverse string current limit Sets the reverse current detection limit.
0.3 A
0 … 0.34 A
100 = 1 A
174.14
String current detection
Enables the string current deviation detection.
Note
: String current detection is available only in
-SX models that includes a string combiner with
DC fuses.
Disable
Disable
0
Enable
1
174.15
String monitor delay
Sets the duration of how long the current
deviation must be above limit before defined
action of the string monitor is triggered.
1 min
0 … 1440 min
1 = 1 min
174.16
Comparison mode
Selects the comparison mode of the string current
deviation detection.
Relative
Absolute
The string current deviation is detected by
comparing the difference in amperes.
0
Relative
The string current deviation is detected by
comparing the difference in percents of reference
value.
1
174.17
Reference type
Selects the current reference type of the string
monitor.
Mean
Max
The reference is the maximum value.
0
Mean
The reference is the mean value.
1
174.18
Relative current limit
Sets the relative string current limit: maximum
allowed difference in percent between each string
and the reference value.
30%
0 … 100%
1 = 1%
174.19
Absolute current limit
Sets the absolute string current limit: maximum
allowed difference in amperes between each
string and the reference value.
1 A
0 … 100 A
1 = 1 A /
10 = 1 A
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Page 4: ......
Page 8: ...8 ...
Page 12: ...12 Service menu ...
Page 36: ...36 Program features ...
Page 100: ...100 Parameters ...
Page 112: ...112 Tools ...
Page 121: ......
Page 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...